HTRUNITGASOIL-A Heater , Unit (Gas and Oil Fired) - Annual

                                                      Man Hours 1
Special Instructions:

1.  Open and tag electric circuit.
2.  Review manufacturer's instructions.


Items to Check & Initial Completion:

1.___ Clean and adjust heater deflector fins and element.
2.___ Clean fan and lubricate motor.
3.___ Clean burner, chamber, thermocouple and control.  (Use a high suction
      vacuum and/or brush.)
4.___ Adjust pilot or electric ignition device.
5.___ Inspect vent and damper operation.
6.___ Operate unit and adjust burner.
7.___ Check operation of safety pilot, gas shut-off valve, and other burner
      safety devices.
8.___ Clean up work site.
9.___ Test the room air around the unit for carbon monoxide emission. Ensure that
      carbon monoxide level averages less than 9ppm/day (parts per million/day).
      If the level of carbon monoxide in the room exceeds 9ppm, turn the unit off
      and repair.  Retest the unit before it is placed back into service.


Tools & Materials:

1.  Standard Tool Kit
2.  Fin comb
3.  Vacuum
4.  C02 analyzer
5.  C0 analyzer
6.  Lubricants.  Consult the Material Safety Data Sheets (MSDS) for hazardous
    ingredients and proper personal protective equipment (PPE).

Table of Contents    |    Next