FPFDRSSWG-Q Fire Pr Fire Doors Stairwells & Exitways (Swinging) - Quarterly

                                                      Man Hours .25
Special Instructions:

The work required by this procedure may cause the activation of an alarm and/or a
supervisory signal.  The office manager and the control center or fire
department that will receive the alarm and/or signal must be notified prior to
start of work.  (See FPAUTOFDCT/AL-A).


Items to Check & Initial Completion:

1.___ Remove all hold-open devices such as fusible links except approved
      electro-magnetic hold open devices.
2.___ Check hang and swing for close fit.  Doors must latch on normal closing
      cycle and have a neat fit.
3.___ Remove any obstructions that retard full swing or movement of door.
4.___ Test operation of panic hardware.  Inspect door coordinates on pairs.
6.___ Check operation of any special devices such as smoke detectors or magnetic
      door releases.
7.___ Inspect door for damage.
8.___ Clean up work area and remove all trash.


Tools & Materials:

1.  Standard Tool Kit