FPFHOSE1.5-A Fire Protection Fire Hose (1.5", Racked in Buildings) - Annual

                                                       Man Hours 1
Special Instructions:

In general, GSA has eliminated racked fire hose in office type buildings.  Such
hose may, however, be maintained in storage facilities. When replacement is made,
the new hose shall be single jacketed, polyester fiber, rubber lined with a
plastic combination spray-straight stream shutoff nozzle. The following work is
to be performed in conjunction with Inspection FPFDHSECONN-A.


Items to Check & Initial Completion:

1.___ Unrack hose and check for wetness or deterioration.
2.___ Uncouple hose and examine it.
3.___ Remove and discard deteriorated hose (justification is required to replace
      this hose).
4.___ Remove nozzle and check for obstruction.
5.___ Recouple and then rerack hose on new folds.
6.___ Clean up work area and remove all trash.


Tools & Materials:

1.  Standard Tool Kit

Table of Contents    |    Next