FPF/SMKDAMP-2Y Fire Protection Fire and Smoke Dampers - 2 Years

                                                         Man Hours .5
Special Instructions:

Fusible link must never be replaced with a piece of wire.  On first inspection,
make sure that damper is not installed backwards.  In all cases, the air movement
should tend to close damper.


Items to Check & Initial Completion:

1.___ Determine that access door is reasonably air tight and latches properly.
2.___ If damper is closed, check for ruptured fusible links, broken attachment or
      hinges, damage, corrosion, etc.
3.___ Remove fusible link and check for proper rating.
4.___ Determine that damper is self-closing and properly latches.  Adjust if
      necessary.
5.___ Check operation of motorized damper control.  Lubricate friction points and
      exercise damper to insure complete freedom of movement.  Remove old or
      excess lubricant.
6.___ Each year, in areas of vibration, install new fusible links of proper
      rating and tensile strength.
7.___ Reinstall fusible link (locations where vibration is not a problem).
8.___ Close access door and check for wind noise.


Tools & Materials:

1.  Standard Tool Kit
2.  Lubricants.

Table of Contents    |    Next