FPFIREALRECDR-W Fire Protection Fire Alarm System - Recorder - Weekly

                                                      Man Hours .25
Items to Check & Initial Completion:

1.___ Clean recording devices.
2.___ Check prewound mechanisms.  Rewind if necessary.
3.___ Examine alignment and tension of paper tape and supply of tape on reels.
      Install new tape when needed.
4.___ Manually move ribbon to prevent ink from drying.  (Papermarking type).
5.___ Inspect for legible punctures or markings on tape.
6.___ Check for correct time on time stamp.  Reset if necessary.


Tools & Materials:

1.  Standard Tool Kit
2.  Ink.

Table of Contents    |    Next