EMERGGEND-A Emergency Generator Diesel Engine - Annual

                                                      Man Hours 3
Special Instructions:

1.  Have approved type fire extinguishers readily available.
2.  Allow no open flame or smoking in area.
3.  Use safety type fuel cans only.
4.  Review manufacturer's instructions.


Items to Check & Initial Completion:

1. ___ Change fuel filters.
2. ___ Inspect and adjust rack on unit injector or fuel distributor pump
        according to manufacturer's instructions.
3. ___ Check governor, adjust for correct speed.
4. ___ Determine fuel level, drain water from tank and inspect for contamination.
       Prior arrangements should be made for local procurement of fuel in
       emergencies.
5. ___ Change engine oil and filter and perform other lubrication on engine and
       generator.
6. ___ Inspect cooling system for leaks, air obstructions, "V" belt tension and
       proper anti-freeze solution.  Make needed adjustments.
7. ___ Inspect generator winding and clean if needed.
8. ___ Clean commutator and collector rings.  Check brush wear and tension in
       accordance with manufacturer's instructions.
9. ___ Inspect generator heaters.
10.___ Remove old oil and diesel fuel from around generator area when
       maintenance is complete.
11.___ Clean engine room and remove all debris.


Tools & Materials:

1.  Standard Tool kit.
2.  Belts.

Table of Contents    |    Next