COILSPHRH-A Coils Preheat, Reheat, Etc (Remote Location) - Annual

Application:

This applies to coils that are not part of an air washer or air handling
unit.


Special Instructions.

1.  Review the Procedure for "Selection, Care, and Use of
    Respiratory Protection."


Items to Check & Initial Completion:

1.___ Vacuum or blow out the fins, coils, etc.
2.___ Remove obstructions to air flow.
3.___ Check coils.  Correct or report any leaks.
4.___ Test and inspect controls that protects coils against freezing.
5.___ Check for rust or corrosion around coil frame and coil mounting bracket.
      Clean, prepare for painting and coat with proper type paint as necessary.


Tools & Materials:

1.  Standard Tool kit.
2.  Vacuum Cleaner wet/dry
3.  Radiator brush
4.  Coil cleaner.  Consult the Material Safety Data Sheets (MSDS) for hazardous
    ingredients and proper personal protective equipment (PPE).
5.  Respirator
6.  Safety goggles
7.  Materials to properly prepare and paint metal.  Consult the MSDS to ensure
    that the paint lead level is 0.06% or less.